Rada Z358-20 has been designed specifically to provide temperature controlled water to emergency fixtures as detailed in ANSI Z358.1-2009.
Z358-20 is a Thermostatic Mixing Valve of “sealed for life”disposable cartridge construction. Compact design and topor bottom blended water outlet make Z358-20 ideal for OEM, new construction and upgrade/retrofit installations.
For Emergency Drench Showers. Rada Z358-20 will pass ANSI specified minimum of 20 gpm/76 lpm (actual 23 gpm/87 lpm) and will flow a minimum of 10 gpm (38 lpm) from direct cold water supply in hot failure mode at 40 psi (2.7 bar) maintained equal inlet supply pressure.
For Emergency Eye Wash Stations. For single or multiplefixture installation, Rada Z358-20 will control accurately atflow rates from 20 gpm (76 lpm) to below 1 gpm (3.8 lpm).
In flow applications between 20 gpm (76 lpm) and 10 gpm(38 lpm), Z358-20 will pass approximately 50% of original flow setting in hot failure mode.
In flow applications between 10 gpm (38 lpm) and 5 gpm (19 lpm), Z358-20 will pass approximately 80% of original flow setting in hot failure mode.In flow applications below 5 gpm (19 lpm), Z358-20 will pass approximately 95% of original flow setting in hot failure mode.
Rada Z358-20 has been designed specifically to provide temperature
controlled water to emergency fixtures as detailed in ANSI Z358.1-2009.
Z358-20 is a Thermostatic Mixing Valve of “sealed for life”disposable
cartridge construction. Compact design and topor bottom blended water
outlet make Z358-20 ideal for OEM, new construction and upgrade/retrofit
installations.
For Emergency Drench Showers. Rada Z358-20 will pass ANSI specified
minimum of 20 gpm/76 lpm (actual 23 gpm/87 lpm) and will flow a minimum
of 10 gpm (38 lpm) from direct cold water supply in hot failure mode at
40 psi (2.7 bar) maintained equal inlet supply pressure.
For Emergency Eye Wash Stations. For single or multiplefixture
installation, Rada Z358-20 will control accurately atflow rates from 20
gpm (76 lpm) to below 1 gpm (3.8 lpm).
In flow applications between 20 gpm (76 lpm) and 10 gpm(38 lpm),
Z358-20 will pass approximately 50% of original flow setting in hot
failure mode.
In flow applications between 10 gpm (38 lpm) and 5 gpm (19 lpm),
Z358-20 will pass approximately 80% of original flow setting in hot
failure mode.In flow applications below 5 gpm (19 lpm), Z358-20 will
pass approximately 95% of original flow setting in hot failure mode.