Steam Tip 10: Recover Heat from Boiler Blowdown


Steam Tip 10: Recover Heat from Boiler Blowdown

Heat can be recovered from boiler blowdown by using a heat exchanger to preheat boiler makeup water. Any boiler with continuous blowdown exceeding 5% of the steam rate is a good candidate for the introduction of blowdown waste heat recovery. Larger energy savings occur with high-pressure boilers. The following table shows the potential for heat recovery from boiler blowdown. 

Example: In a plant where the fuel cost is $8.00 per million Btu ($8.00/MMBtu), a continuous blowdown rate of 3,200 pounds per hour (lb/hr) is maintained to avoid the buildup of high concentrations of dissolved solids. What are the annual savings if a makeup water heat exchanger is installed that recovers 90% of the blowdown energy losses? The 80% efficient boiler produces 50,000 pounds per hour (lb/hr) of 150-pounds-per-square-inch-gauge (psig) steam. It operates for 8,000 hours per year. The blowdown ratio is: 

Blowdown Ration = 3,200 ÷ (3,200 + 50,000) = 6.0%

From the table, the heat recoverable corresponding to a 6% blowdown ratio with a 150-psig boiler operating pressure is 1.7 MMBtu/hr. Since the table is based on a steam production rate of 100,000 lb/hr, the annual savings for this plant are: 

Annual Energy Savings =
 [1.7 MMBtu/hr x (50,000 lb/hr/100,000 lb/hr) x 8,000 hr/yr]/0.80 = 8,500 MMBtu 

Annual Cost Savings =
8,500 MMBtu/yr x $8.00/MMBtu = $68,000

Blowdown Energy Recovery: Blowdown waste heat can be recovered with a heat exchanger, a flash tank, or flash tank in combination with a heat exchanger. Lowering the pressure in a flash tank allows a portion of the blowdown to be converted into low-pressure steam. This low-pressure steam is most typically used in deaerators. Drain water from the flash tank is then routed through a heat exchanger. Cooling the blowdown has the additional advantage of helping to comply with local codes limiting the discharge of high-temperature liquids into the sewer system. 

For additional information on heat recovery, contact the team at Campbell-Sevey or download this Steam Tip sheet for suggested actions and resources. 

Published by the U.S. Department of Energy.

No comments (Add your own)

Add a New Comment


code
 

Comment Guidelines: No HTML is allowed. Off-topic or inappropriate comments will be edited or deleted. Thanks.

Subscribe to our CS Update Newsletter: Send Me The Latest News

952-935-2345  emailmain@campbell-sevey.com  address15350 Minnetonka Blvd., Minnetonka, MN 55345

Products We Carry

GENERATION
  • Hot Water Boilers
  • Watertube Steam Boilers
  • Firetube Steam Boilers
  • Deaerators
  • Heat Recovery Steam Generators (HRSG’s)
  • Automatic Recirculation Valves
  • Economizers
  • Gas-Fired Water Heaters
  • Gas-Fired Humidifiers
  • Boiler/Generator Flue Stacks
  • Continuous Emissions Monitors (CEMS)
DISTRIBUTION
  • Pressure Reducing Valves
  • Safety and Relief Valves
  • Control Valves
  • Pressure Independent Control Valves
  • Expansion Joints, Guides, Anchors
  • Flash Tanks
  • Flow Meters
  • Balancing Valves
  • Check Valves
  • Separators
  • Pumps
  • Pressure Booster Systems
  • Piston Valves
UTILIZATION
  • Heating/Cooling Coils
  • Plate and Frame Heat Exchangers
  • Shell and Tube Exchangers
  • Water Heaters
  • Steam Humidifiers
  • Vacuum Systems
  • Condensers
  • Steam Traps
  • Wireless Steam Trap Monitors
  • Tube Bundles
  • Direct Gas-Fired Space Heaters
  • Direct Gas-Fired Make-Up Air Units
  • Unit Heaters
  • Strainers
  • Air Vents
  • Liquid Drainers
  • Heat Transfer Packages
  • Digital Water Mixing Valves
  • Air Cooled Condensers/Dry Coolers
  • Steam Filters
RETURN
  • Electric Condensate Pumps
  • Steam/Air-Powered Condensate Pumps
  • Packaged Condensate Pump Skids