Follow us on Have any questions? Just call us 952-935-2345

News & Events

Deaerators in Industrial Steam Systems


Deaerators in Industrial Steam Systems

(from U.S. Department of Energy: Improving Steam System Performance)

Deaerators are mechanical devices that remove dissolved gases from boiler feed-water. Deaeration protects the steam system from the effects of corrosive gases. It accomplishes this by reducing the concentration of dissolved oxygen and carbon dioxide to a level where corrosion is minimized. A dissolved oxygen level of 5 parts per billion (ppb) or lower is needed to prevent corrosion in most high pressure (>200 psig) boilers. While oxygen concentrations of up to 43 ppb may be tolerated in low pressure boilers, equipment life is extended at little or no cost by limiting the oxygen concentration to 5 ppb. Dissolved carbon dioxide is essentially completely removed by the deaerator.

How They Work
The design of an effective deaeration system depends upon the amount of gases to be removed and the final gas (O2) concentration desired. This in turn depends upon the ratio of boiler feedwater makeup to returned condensate and the operating pressure of the deaerator.

Deaerators use steam to heat the water to the full saturation temperature corresponding to the steam pressure in the deaerator and to scrub out and carry away dissolved gases. Steam flow may be parallel, cross, or counter to the water flow. The deaerator consists of a deaeration section, a storage tank, and a vent. In the deaeration section, steam bubbles through the water, both heating and agitating it. Steam is cooled by incoming water and condensed at the vent condenser. Non-condensable gases and some steam are released through the vent.

Steam provided to the deaerator provides physical stripping action and heats the mixture of returned condensate and boiler feedwater makeup to saturation temperature. Most of the steam will condense, but a small fraction (usually 5 to 14%) must be vented to accommodate the stripping requirements. Normal design practice is to calculate the steam required for heating, and then make sure that the flow is sufficient for stripping as well. If the condensate return rate is high (>80%) and the condensate pressure is high compared to the deaerator pressure, then very little steam is needed for heating, and provisions may be made for condensing the surplus flash steam.

Deaerator Steam Consumption
The deaerator steam consumption is equal to the steam required to heat incoming water to its saturation temperature, plus the amount vented with the non-condensable gases, less any flashed steam from hot condensate or steam losses through failed traps. The heat balance calculation is made with the incoming water at its lowest expected temperature. The vent rate is a function of deaerator type, size (rated feedwater capacity), and the amount of makeup water. The operating vent rate is at its maximum with the introduction of cold, oxygen-rich makeup water.

Additional Benefits
Deaerators provide the water storage capacity and the net positive suction head neces-
sary at the boiler feed pump inlet. Returned condensate is mixed with makeup water
within the deaerator. Operating temperatures range from 215°F to over 350°F, which reduces the thermal shock on downstream preheating equipment and the boiler.

Insulation
The deaerator section and storage tank and all piping conveying hot water or steam should be adequately insulated to prevent the condensation of steam and loss of heat.

Function Clarification
The deaerator is designed to remove oxygen that is dissolved in the entering water, not entrained air. Sources of “free air” include loose piping connections on the suction side of pumps and improper pump packing.

Pressure Fluctuations
Sudden increases in free or “flash” steam can cause a spike in deaerator vessel pres- sure, resulting in re-oxgenation of the feedwater. A dedicated pressure-regulating valve should be provided to maintain the deaerator at a constant pressure.

Suggested Actions

  • Deaerator steam requirements should be re-examined following the retrofit of steam distribution system, condensate return, or heat recovery energy conservation measures.
  • Install continuous dissolved oxygen monitoring devices to aid in identifying operating practices that result in poor oxygen removal.

Contact Campbell-Sevey to see if deaerators can benefit your current system.

 

 

 

2 comments (Add your own)

1. OlegCeaby wrote:

Sun, February 12, 2017 @ 7:56 AM

2. Irinanog wrote:

Tue, February 14, 2017 @ 11:41 PM

Add a New Comment


code
 

Comment Guidelines: No HTML is allowed. Off-topic or inappropriate comments will be edited or deleted. Thanks.

Subscribe to our CS Update Newsletter: Send Me The Latest News

952-935-2345  emailmain@campbell-sevey.com  address15350 Minnetonka Blvd., Minnetonka, MN 55345

Products We Carry

GENERATION
  • Hot Water Boilers
  • Watertube Steam Boilers
  • Firetube Steam Boilers
  • Deaerators
  • Heat Recovery Steam Generators (HRSG’s)
  • Automatic Recirculation Valves
  • Economizers
  • Gas-Fired Water Heaters
  • Gas-Fired Humidifiers
  • Boiler/Generator Flue Stacks
  • Continuous Emissions Monitors (CEMS)
DISTRIBUTION
  • Pressure Reducing Valves
  • Safety and Relief Valves
  • Control Valves
  • Pressure Independent Control Valves
  • Expansion Joints, Guides, Anchors
  • Flash Tanks
  • Flow Meters
  • Balancing Valves
  • Check Valves
  • Separators
  • Pumps
  • Pressure Booster Systems
  • Piston Valves
UTILIZATION
  • Heating/Cooling Coils
  • Plate and Frame Heat Exchangers
  • Shell and Tube Exchangers
  • Water Heaters
  • Steam Humidifiers
  • Vacuum Systems
  • Condensers
  • Steam Traps
  • Wireless Steam Trap Monitors
  • Tube Bundles
  • Direct Gas-Fired Space Heaters
  • Direct Gas-Fired Make-Up Air Units
  • Unit Heaters
  • Strainers
  • Air Vents
  • Liquid Drainers
  • Heat Transfer Packages
  • Digital Water Mixing Valves
  • Air Cooled Condensers/Dry Coolers
  • Steam Filters
RETURN
  • Electric Condensate Pumps
  • Steam/Air-Powered Condensate Pumps
  • Packaged Condensate Pump Skids